Behind-the-Meter Storage • 500 kWh to 50 MWh+

Industrial & Commercial (C&I) Battery Energy Storage Solutions

Engineering-led behind-the-meter BESS for manufacturing plants, logistics parks, and commercial campuses—managing peak kVA demand charges, Time-of-Day spreads, DG-PV synchronization, and HT statutory compliance.

Peak kVA Demand Shaving ToD Tariff Arbitrage DG-PV-BESS Sync 11 kV / 33 kV CEIG Ready
UE-CI-001 • BTM Industrial HT SLD 415 V / 11 kV / 33 kV
Behind-the-Meter Industrial HT Single-Line Diagram showing Grid Incomer, Solar PV, DG Set, BESS PCS, Reverse-Power Relay, and Factory Load Bus DISCOM INCOMER 11 / 33 kV Grid Anti-Islanding & Rev-Power PLANT MAIN BUSBAR 11 kV / 33 kV / 415 V PCC Bus Synchronized Multi-Source Protection STORAGE BESS + PCS Peak Shave & ToD CAPTIVE Solar PV Zero-Export BACKUP DG Set Min-Load Sync OEM EMS / SCADA 15-Min Load Control Modbus / IEC 61850 CRITICAL & PROCESS PLANT LOADS Manufacturing Lines, Chillers, Compressors & HVAC CEIG >650 V statutory compliance • NFPA 855 outdoor setbacks • No vendor lock-in

Industrial plants and commercial campuses face compounding power cost and reliability pressures: rising Time-of-Day (ToD) evening surcharges, monthly kVA maximum-demand ratchets triggered by brief motor or furnace starts, grid voltage sags that trip sensitive PLC lines, and high diesel generator (DG) fuel spend during feeder outages.

Ultrathon Electric designs and delivers behind-the-meter (BTM) Industrial & C&I BESS (500 kWh to 50 MWh+) grounded in 15-minute load-interval engineering, HT protection coordination (11 kV / 33 kV), and statutory CEIG/fire-safety compliance—rather than off-the-shelf cabinet promises.

Site-Specific Economics Disclosure
C&I BESS financial returns depend entirely on state-specific DISCOM ToD tariff spreads, kVA demand charge structures, daily cycle frequency, and captive/open-access solar pairing. Any preliminary payback or savings figures are strictly illustrative until validated against 12 months of your facility's 15-minute interval load data via our BESS Assessment Tool.
Industrial Applications

Core Behind-the-Meter C&I BESS Use Cases

Engineered around industrial load profiles, HT switchgear boundaries, and captive renewable integration.

01 • Demand Control

Peak kVA Demand Shaving

Discharging during brief 15-minute integration windows when plant demand spikes, preventing monthly contract-demand ratchets and penalty surcharges.

02 • Tariff Optimization

Time-of-Day (ToD) Arbitrage

Charging from off-peak solar or low-tariff night slots and discharging during peak evening ToD blocks to reduce net energy procurement cost.

03 • Captive Solar

Solar + BESS Captive Firming

Absorbing excess rooftop or open-access solar under zero-export constraints and shifting clean generation into evening and night-shift production hours.

04 • DG Optimization

DG-PV-BESS Synchronization

Coordinating BESS PCS with diesel generators to carry step loads, maintain minimum DG loading (preventing wet-stacking), and reduce diesel runtime.

Sizing & Safety

C&I BESS Use-Case Sizing & Statutory Matrix

Matching storage duration, C-rate, and protection architecture to industrial operating regimes.

C&I BESS Use-Case Sizing Guide
Use Case Typical Duration Typical C-Rate SoC Operating Band Key Protection / Control Requirement
Peak kVA Demand Shaving 1 hr – 2 hr 0.5C – 1.0C 10% – 90% SoC Fast 15-min integration metering & load-prediction setpoint
ToD Arbitrage & Solar Shifting 2 hr – 4 hr 0.25C – 0.5C 10% – 90% SoC Zero-export / reverse-power relay at DISCOM incomer
DG-PV-BESS Hybrid & Backup 2 hr – 4 hr+ 0.5C 20% – 90% Reserve IEEE 1547 anti-islanding, STS / AMF sync & DG min-load guard
CEIG >650 V Threshold & CEA Chapter X-A (Effective 1 April 2027)
Under Indian electrical safety rules, CEA Safety Regulations Chapter X-A applies to BESS connected above 650 V (Regs 122(A)–122(M), e.g., 11 kV / 33 kV industrial HT tie-ins) and at or below 650 V (Reg 122(N)), and is future-effective from 1 April 2027. Present HT installations are governed by existing CEA Safety Regulations (2023), State CEIG inspections, IEEE 1547-2018 anti-islanding rules, and NFPA 855 / UL 9540A spatial setbacks.
Execution Workflow

C&I BESS Engineering & Delivery Process

Data-first load audit through HT protection design, CEIG clearance, and plant SCADA integration.

  1. 01 • Load Audit

    15-Min Interval Analysis

    Audit 12-month 15/30-min load curves, ToD tariff bills, kVA demand spikes, and existing solar/DG single-line diagrams.

  2. 02 • Sizing & ROI

    Tariff & Sizing Model

    Simulate kW/kWh sizing, 10%–90% SoC cycling, degradation, and site-specific economics without unverified generic claims.

  3. 03 • Design & CEIG

    HT Protection & HMA

    Engineer 11 kV/33 kV tie-in, reverse-power/anti-islanding relays, NFPA 855 outdoor setbacks, and CEIG/Fire NOC dossiers.

  4. 04 • EPC & SAT

    Installation & SCADA Sync

    Civil foundations, OEM container/PCS erection, Modbus/IEC 61850 EMS tie-in to plant SCADA, and full SAT commissioning.

Technical FAQs

Frequently Asked Questions: Industrial & C&I BESS

How do I determine the right kW and kWh BESS size for my factory or commercial facility?
Sizing starts with 12 months of 15-minute or 30-minute interval load data, contract demand (kVA) ratchets, Time-of-Day (ToD) tariff slabs, and existing solar/DG profiles. Power (kW) is sized to clip peak demand spikes or support critical loads, while energy (kWh) is sized for the target discharge duration and usable State-of-Charge (SoC) window (commonly 10%–90%).
Does a behind-the-meter C&I BESS require CEIG and DISCOM approvals?
Yes, for HT (11 kV / 33 kV) industrial installations or systems connected above 650 V, State Electrical Inspectorate / CEIG statutory inspection and DISCOM anti-islanding / reverse-power protection coordination are required. Systems at or below 650 V still require compliance with baseline electrical and product safety standards.
Can BESS synchronize with existing diesel generators (DGs) and rooftop solar?
Yes. An OEM-supplied microgrid/hybrid EMS coordinates BESS PCS, rooftop solar inverters, and existing DG controllers via reverse-power protection, spinning-reserve logic, and minimum-load management so solar output is maximized while preventing DG wet-stacking or back-feeding.
What fire safety clearances and setbacks are required to install BESS inside an industrial campus?
Outdoor containerized siting with NFPA 855 spatial setbacks from buildings, lot lines, and exposures—backed by UL 9540A thermal runaway propagation test data and a site-specific Hazard Mitigation Analysis (HMA)—is recommended wherever campus space permits. Local Fire NOC and CEIG rules govern final approval.
How does Ultrathon integrate BESS EMS with existing plant SCADA/BMS without vendor lock-in?
Ultrathon does not sell proprietary EMS software. We specify open-protocol, commercially available OEM EMS platforms (Modbus TCP, IEC 61850, or OPC-UA) and integrate them with your existing plant SCADA, AMF panels, and power-quality meters.
Behind-the-Meter C&I Storage

Audit Your Factory Load Profile for BESS

Share your 15-minute load interval data and ToD tariff schedule for an engineering-led C&I BESS sizing and HT integration study.