1. Inadequate Physical Separation: Placing oil-filled step-up transformers within 3 meters of battery container walls without a 2-hour fire-rated RCC or masonry blast barrier. Remedy: Design 3m separation or 2-hour blast walls during initial layout drafting.
2. Grounding Neutral Overlap: Combining transformer neutral earthing with lightning arrester grounding. Remedy: Maintain separate, dedicated, non-interlinked electrode pits with minimum 3-meter physical separation between electrodes.
3. Emergency Power Off (EPO) Integration: Lack of externally accessible, lockable emergency battery trip pushbuttons outside container hazardous zones. Remedy: Integrate hardwired dual-channel shunt-trip wiring to the main DC breaker and 33kV vacuum circuit breaker.